A planned preventative maintenance (PPM) schedule for a block of flats lists every asset in the common parts, what needs checking, how often, who does it and where the record is kept. Build it in two layers: first the checks that law or official guidance sets a frequency for, such as fire doors, gas appliances, lifts and water systems, then the routine care that keeps the roof, drainage, door entry and plant working.
The legal layer depends on the building. A two storey block and an 18 metre tower share some duties but not others, so the starting point is knowing the height, what plant is installed and who the responsible person is.
Start with an asset register
- Building height and number of storeys, measured to the top occupied floor, because several fire safety duties start at 11 metres and 18 metres
- Fire safety systems: alarm and detection, emergency lighting, smoke ventilation, dry or wet risers, fire doors in the common parts and flat entrance doors
- Gas plant the landlord provides, such as communal boilers, with every appliance and flue listed
- Water systems: cold water storage tanks, hot water cylinders or calorifiers, booster pumps and little-used outlets
- Lifts, automatic doors, gates and car park barriers
- Door entry, access control and CCTV
- Roofs, gutters, roof outlets, drainage and external fabric
- The current fire risk assessment, the last electrical report and manufacturer servicing requirements
The statutory core
These items set the backbone of the calendar. Frequencies below are minimums from the regulations or official guidance, and your fire risk assessment or the last inspection report can require more.
- Fire risk assessment: the Regulatory Reform (Fire Safety) Order 2005 requires it to be reviewed regularly, and since 1 October 2023 every responsible person in England must keep a written record of the assessment and its findings
- Fire doors in buildings over 11 metres: quarterly checks of all fire doors in the common parts, including self-closing devices, and annual checks of flat entrance doors on a best endeavours basis, with fire door information given to residents every year (see our Fire Safety (England) Regulations 2022 guide)
- Buildings of at least 18 metres or seven storeys: monthly checks of firefighters lifts, evacuation lifts and essential fire-fighting equipment such as rising mains, smoke control and fire alarm systems, with results recorded so residents can see them and faults not fixed within 24 hours reported to the fire and rescue service
- Emergency lighting: a monthly function test and an annual full duration test, following BS 5266-1 (see our emergency lighting testing guide)
- Fire alarm and detection: tested and serviced at the intervals set by the system's British Standard and your fire risk assessment, with every test logged
- Gas: each appliance and flue a landlord provides checked by a Gas Safe registered engineer at intervals of no more than 12 months, with records kept for at least two years and a copy given to existing tenants within 28 days (see our gas safety guide)
- Electrics: in let flats, the fixed installation inspected and tested at least every five years, or sooner if the last report says so (see our EICR guide)
- Water: a legionella risk assessment reviewed periodically and whenever something changes, with monitoring such as monthly temperature checks at sentinel outlets, and HSE recommends keeping monitoring records for at least five years (see our legionella guide)
- Lifts: where a lift is used by people at work, the Lifting Operations and Lifting Equipment Regulations 1998 require a thorough examination at least every six months for equipment that lifts people
Residential lifts need care. HSE says these regulations may not apply where a passenger lift is not used by people at work, but whoever controls the lift in connection with their business still has duties under the Health and Safety at Work etc. Act 1974, and a similar regime of maintenance and examination may be entirely reasonably practicable. Keeping six monthly thorough examinations in the schedule, alongside routine servicing, is the safer default.
Then add the building itself
These rarely have a legal frequency, so set them from manufacturer instructions, condition and what reactive call-outs tell you. Typical items:
- Gutters, roof outlets and drains cleared before winter, and a roof inspection after storms (our winter maintenance checklist covers the seasonal work)
- Door entry, access control, gates and barriers serviced, with fobs and codes audited
- Communal lighting, timers and sensors checked on a set round
- Pumps, extract fans and ventilation serviced to the manufacturer's schedule
- CCTV checked for coverage, recording and retention settings
- External fabric, balconies and walkways inspected and photographed so defects can be tracked
Turning the list into a schedule
- Group tasks into monthly, quarterly, six monthly, annual and five yearly visits
- Align due dates where the rules allow: gas checks done up to two months early keep their original anniversary
- Plan access early for anything inside flats, such as entrance door checks, and log every attempt
- Keep one register of each task, its last and next date, the certificate and any remedial action, so overdue items are visible
- Review reactive repair data every quarter and move recurring faults into the planned schedule
Local fire services publish their own guidance: London Fire Brigade explains the 2022 regulations by building type, and Greater Manchester and Merseyside fire and rescue services run online routes for reporting high-rise faults. In leasehold blocks, a maintenance contract longer than 12 months where any leaseholder pays more than £100 a year is a qualifying long-term agreement and needs section 20 consultation first.
How Apex helps
Apex Options builds and runs planned preventative maintenance schedules for residential and commercial buildings, with on-site delivery in London, Liverpool, Manchester, Greater Manchester and Cheshire. We start from your asset register and fire risk assessment, combine visits where we can and keep certificates, logs and remedial actions together under fire safety and compliance. This guide is general information, not legal advice, so confirm your building's specific duties with a qualified professional.
Sources
- GOV.UK: Fire Safety (England) Regulations 2022, fact sheet on fire doors (regulation 10)
- GOV.UK: Fire Safety (England) Regulations 2022, fact sheet on lifts and essential fire-fighting equipment (regulation 7)
- legislation.gov.uk: Building Safety Act 2022, section 156
- HSE: Gas safety check records and what to keep
- legislation.gov.uk: Gas Safety (Installation and Use) Regulations 1998, regulation 36
- GOV.UK: Electrical safety standards in the private and social rented sectors
- HSE: Legionella and landlords' responsibilities
- HSE: Legionella, things to consider
- HSE: Thorough examinations of lifting equipment
- HSE: Passenger lifts
- London Fire Brigade: Fire Safety (England) Regulations 2022
- Greater Manchester Fire and Rescue Service: faults and repairs
- Merseyside Fire and Rescue Service: fault and information reporting